Booster set operating limits

Type of pumped liquids

Water with no gas or aggressive substances

Maximum pumped liquid temperature

+35°C for domestic uses (EN 60335-2-41)

Minimum pumped liquid temperature

1°C to avoid icing

Operating ambient temperature

+5°C at 40°C

Relative humidity

Max 50% at 40°C

Air impurities

The air must be clean and free of acid vapours, corrosive gases and excessive amounts of dust.

Storage temperature

+5°C to 40°C

Suction conditions

Minimum positive pressure 0.1 bar. Max. 0.5 bar

Conversion factors

Flow rate

l/min ÷ 60 = l/sec

m3/hour ÷ 3.6 = l/sec

GPM ÷ 13.2 = l/sec

kg/sec = l/sec

Figures are given for clean cold water.

Pressure

m Hd ÷ 10.2 = bar

PSI ÷ 14.47 = bar

kPa ÷ 100 = bar

kg/cm2 ÷ 10.2 = bar

Figures are given for clean cold water.

Variable-speed flow, head and power calculations

Flow rate

Flow rate at reduced speed = (reduced speed ÷ full speed) X flow rate at full speed

Head

Head at reduced speed = (reduced speed ÷ full speed)2 X head at full speed

Power

Power at reduced speed = (reduced speed ÷ full speed)3 X power at full speed