ResiSHIELD® DH Model Options
DH0302-EL
0.37
230/1/50
2.5
DH0303-EL
0.55
230/1/50
3
DH0304-EL
0.55
230/1/50
3.7
DH0305-EL
0.75
230/1/50
4.3
DH0502-EL
0.55
230/1/50
3.6
DH0503-EL
0.55
230/1/50
3.6
DH0504-EL
1.1
230/1/50
6.3
DH0505-EL
1.1
230/1/50
6.3
DH1002-EL
0.75
230/1/50
4.6
DH1003-EL
1.1
230/1/50
6.3
DH1004-EL
1.5
230/1/50
8.4
DH0302E-EL-B
0.33
230/1/50
2.5
DH0303E-EL-B
0.45
230/1/50
3
DH0304E-EL-B
0.55
230/1/50
3.7
DH0305E-EL-B
0.75
230/1/50
4.3
DH0502E-EL-B
0.45
230/1/50
3
DH0503E-EL-B
0.55
230/1/50
3.9
DH0504E-EL-B
0.9
230/1/50
5.3
DH0505E-EL-B
1.1
230/1/50
6.2
DH1002E-EL-B
0.75
230/1/50
4.3
DH1003E-EL-B
1.1
230/1/50
6.3
DH1004E-EL-B
1.5
230/1/50
8.2
ResiSHIELD® DH Resources
Dutypoint ResiSHIELD DH Buzzer datasheet.
A technical brochure for the ResiSHIELD DH. Last updated Oct 2024.
Installation, operation and maintenance manual for the 2024 DH O&M. Last updated Oct 2024.
Installation, operation and maintenance manual for the 2023 DH O&M with H500 type controller (with screen).
Installation, operation and maintenance manual for the 2023 DH O&M with WD2 type controller (no screen).
ResiSHIELD® DH Specification
Product overview
– Housed within an ultra-compact, aesthetically pleasing powder-coated mild steel enclosure, providing ultimate protection from accidental damage
– Removable front cover for easy maintenance access
– Wall mountable
– Fully compliant with BS 9251:2021
– Includes 2no pressure switches, 1no LPCB-approved flow switch, 1no auto test solenoid all pre-fitted and pre-tested
– High-quality cast stainless steel manifold assembly
– Volt-free contacts included for fire alarm and range of faults
– Intuitive LCD controller with full number keypad makes set up and commissioning quick and user friendly
– Can be connected directly to the mains water supply*
– Common models are available from stock
– Comes pre-fitted with 1.5 m FP200 power supply cable
*Permission should be obtained from the local water authority before installing any pump system directly to the mains that is designed to operate at any higher than 12 l/min. Where connecting a ResiSHIELD pump set directly to the mains, the pump set should be selected such that its maximum head is at least 1 bar higher than the available mains pressure, and the pressure switches should both be set higher than the mains pressure in order for the weekly self-test functionality to perform correctly in accordance with BS 9251:2021.
Optional Extras
– Integrated battery-powered audible alarm
– Pre-wired multicore signal cable for common fault and fire signals
– Right-hand inlet version
Range Performance
Flow range
30 – 200 l/min
Max system pressure
10 bar
Material Specification
Manifold
Duplex stainless steel
Pump casing
AISI 304 stainless steel
Pump impellers
AISI 304 stainless steel
Base plate/enclosure
Powder-coated mild steel