Product overview
– Multistage vertical pumps
– Low-water cut-out contacts in panel
– Anti-vibration mounts reduce system noise
– Pressure set point adjustment
– Hours run recorders
– Local electrical isolation and MCB protection
– IP55-rated control panel allows for simple and safe maintenance
– Cyclic duty changeover ensures even wear across pumps
– Common fault volt-free contact for connection to building management systems
– RS485 connections for connection to Modbus
Options
– PN25 option available
– Motor anti-condensation heaters
– Control panel specification upgrades
Number of pumps
2, 3 or 4
Pressure range
2.5 – 16 bar
Max system pressure
16 bar
Controller type
Motor-mounted inverter
Max system temperature
40°C*
Noise data
Motor at 2900 rpm < 70LpA (dB +/-2)**
*Available for higher temperature if required. **More specific details available on request.
Manifolds
AISI 304 stainless steel
Isolation valves
Nickel-plated brass
Non-return valves
AISI 304 stainless steel
Pressure transducers
AISI 304 stainless steel
Pump casing
AISI 304 stainless steel/cast iron (in certain selections)
Pump impellers
AISI 304 stainless steel
Mechanical seals
Silicon carbide, graphite, EPDM
Pressure vessels
WRAS approved
Base plate
Powder-coated mild steel
VMV2-05-6V110D02
11
400/3/50
40
VMV2-07-6V110D02
11
400/3/50
40
VMV2-10-5V040L02
4
400/3/50
16
VMV2-10-5V055L02
5.5
400/3/50
20
VMV2-10-5V075L03
7.5
400/3/50
28
VMV2-10-5V110L04
11
400/3/50
40
VMV2-15-5V075L01
7.5
400/3/50
28
VMV2-15-5V110L02
11
400/3/50
40
VMV2-20-5V110L02
11
400/3/50
40
VMV3-05-6V110D02
11
400/3/50
60
VMV3-07-6V110D02
11
400/3/50
60
VMV3-07-6V150D01
15
400/3/50
81
VMV3-10-5V040L02
4
400/3/50
24
VMV3-10-5V055L02
5.5
400/3/50
30
VMV3-10-5V075L03
7.5
400/3/50
42
VMV3-10-5V110L04
11
400/3/50
60
VMV3-10-5V150L05
15
400/3/50
81
VMV3-15-5H185L02
18.5
400/3/50
99
VMV3-15-5H220L02
22
400/3/50
126
VMV3-15-5V055L01
5.5
400/3/50
30
VMV3-15-5V075L01
7.5
400/3/50
42
VMV3-15-5V110L02
11
400/3/50
60
VMV3-15-5V150L02
15
400/3/50
81
VMV4-05-6V030D01
3
400/3/50
24
VMV4-05-6V040D01
4
400/3/50
28
VMV4-05-6V055D01
5.5
400/3/50
44
VMV4-05-6V075D01
7.5
400/3/50
60
VMV4-05-6V110D02
11
400/3/50
80
VMV4-07-6V055D01
5.5
400/3/50
44
VMV4-07-6V075D01
7.5
400/3/50
60
VMV4-07-6V110D02
11
400/3/50
80
VMV4-07-6V150D01
15
400/3/50
108
VMV4-10-5V055L02
5.5
400/3/50
40
VMV4-10-5V075L03
7.5
400/3/50
56
VMV4-10-5V110L04
11
400/3/50
80
VMV4-10-5V150L05
15
400/3/50
108
VMV4-15-5H185L02
18.5
400/3/50
132
VMV4-15-5H220L02
22
400/3/50
168
VMV4-15-5V110L02
11
400/3/50
80
VMV4-15-5V150L02
15
400/3/50
108
Brochure
A technical overview of the Dutypoint VMV. |
|
Case studies
Working on a high-rise luxury residential tower development in the heart of London’s Docklands |
|
Certificates
The VMV range of booster sets are WRAS-approved products. Certificate number 1310318. |
|
Manuals
VMV Booster Set Operation and Maintenance Manual. |
|
VMV Booster Set Operation and Maintenance Manual with Hydrovar Inverter. |
|
Control Panel Diagrams
Control Panel Wiring Diagram for Twin Pump, Single Phase (240v) Booster Sets |
|
Control Panel Wiring Diagram for Twin Pump, Three Phase (400v) Booster Sets |
|
Control Panel Wiring Diagram for Triple Pump, Single Phase (240v) Booster Sets |
|
Control Panel Wiring Diagram for Triple Pump, Three Phase (400v) Booster Sets |
|
Control Panel Wiring Diagram for Four Pump, Three Phase (400v) Booster Sets |
|
Control Panel Wiring Diagram for Six Pump, Three Phase (400v) Booster Sets |
|
Control Panel Wiring Diagram for Eight Pump, Three Phase (400v) Booster Sets |
|
Configuration Selection Forms
Twin pump VMV configuration selection form |
|
Triple pump VMV configuration selection form |
|
Four pump VMV configuration selection form |
|
Five pump VMV configuration selection form |
|
Six pump VMV configuration selection form |
|